Are these 45-degree wall braces structurally important or just for convenience?












4














I was helping a friend expand the width of a closet door, and when we pulled the drywall off the interior wall frame, we noticed some 45-degree wall braces in the interior wall.



I am pretty sure they are just for convenience during construction (e.g. a bother to remove once the frames are fully built or just there for drywall to be nailed into).



However, I am not an expert, so I wasn't sure if these were structural (maybe some type of shear wall support?) or not. In case it matters, the house was built in 1951 and is in western Georgia. All the wooden beams, including the angled ones, are held in place with 4inch nails.



Are these angle braces safe to remove and leave out? The entire cutaway area (sans drywall) would be a closet door with a frame of two 2x4s above and a vertical 2x4 on either side.



Head-on view



Angle view with window/exterior wall in frame



Closeup view










share|improve this question



























    4














    I was helping a friend expand the width of a closet door, and when we pulled the drywall off the interior wall frame, we noticed some 45-degree wall braces in the interior wall.



    I am pretty sure they are just for convenience during construction (e.g. a bother to remove once the frames are fully built or just there for drywall to be nailed into).



    However, I am not an expert, so I wasn't sure if these were structural (maybe some type of shear wall support?) or not. In case it matters, the house was built in 1951 and is in western Georgia. All the wooden beams, including the angled ones, are held in place with 4inch nails.



    Are these angle braces safe to remove and leave out? The entire cutaway area (sans drywall) would be a closet door with a frame of two 2x4s above and a vertical 2x4 on either side.



    Head-on view



    Angle view with window/exterior wall in frame



    Closeup view










    share|improve this question

























      4












      4








      4







      I was helping a friend expand the width of a closet door, and when we pulled the drywall off the interior wall frame, we noticed some 45-degree wall braces in the interior wall.



      I am pretty sure they are just for convenience during construction (e.g. a bother to remove once the frames are fully built or just there for drywall to be nailed into).



      However, I am not an expert, so I wasn't sure if these were structural (maybe some type of shear wall support?) or not. In case it matters, the house was built in 1951 and is in western Georgia. All the wooden beams, including the angled ones, are held in place with 4inch nails.



      Are these angle braces safe to remove and leave out? The entire cutaway area (sans drywall) would be a closet door with a frame of two 2x4s above and a vertical 2x4 on either side.



      Head-on view



      Angle view with window/exterior wall in frame



      Closeup view










      share|improve this question













      I was helping a friend expand the width of a closet door, and when we pulled the drywall off the interior wall frame, we noticed some 45-degree wall braces in the interior wall.



      I am pretty sure they are just for convenience during construction (e.g. a bother to remove once the frames are fully built or just there for drywall to be nailed into).



      However, I am not an expert, so I wasn't sure if these were structural (maybe some type of shear wall support?) or not. In case it matters, the house was built in 1951 and is in western Georgia. All the wooden beams, including the angled ones, are held in place with 4inch nails.



      Are these angle braces safe to remove and leave out? The entire cutaway area (sans drywall) would be a closet door with a frame of two 2x4s above and a vertical 2x4 on either side.



      Head-on view



      Angle view with window/exterior wall in frame



      Closeup view







      walls structural construction






      share|improve this question













      share|improve this question











      share|improve this question




      share|improve this question










      asked 5 hours ago









      TylerH

      1627




      1627






















          2 Answers
          2






          active

          oldest

          votes


















          2














          Temporary braces are nailed to the face of the wall, not fit into it. That was intended as a structural member by the carpenter.



          That said, it's almost certainly not critical. The entirety of the other nearby walls and the roof structure likely provide many times what that one brace does in diagonal support. Also, you don't see that technique used anymore.



          I wouldn't hesitate to remove the portion that impedes your progress.



          I do suggest a doubled stud, however, and you might want to orient at least one of your header members vertically, for stiffness.






          share|improve this answer





















          • When you say orient one header vertically, do you mean like |_ as opposed to || (looking down the long axis of the headers)?
            – TylerH
            2 hours ago



















          2














          Sometimes framing of a short internal wall that TEE's into an exterior wall is braced that way if the exterior wall is:




          1. The exterior wall extends a long distance on either side of the TEE

          2. And the exterior wall is parallel to ceiling joists and floor joists

          3. And has a high gable end wall above this area.


          Intention was to eliminate a lot of flex in the exterior wall both during construction and when there is possibility of large gusty wind loads on the wall. You will see less of this with much construction moving toward 2x6 studding for exterior walls. Metal X banding nailed to the face of the studs is also a better way to achieve this result.



          Repeating from Isherwood. Make sure to put double stud at the left and right side of your opening. A single 2x4 is just not stiff enough and you will really appreciate it being there when you come to install door casing or trim.






          share|improve this answer





















            Your Answer








            StackExchange.ready(function() {
            var channelOptions = {
            tags: "".split(" "),
            id: "73"
            };
            initTagRenderer("".split(" "), "".split(" "), channelOptions);

            StackExchange.using("externalEditor", function() {
            // Have to fire editor after snippets, if snippets enabled
            if (StackExchange.settings.snippets.snippetsEnabled) {
            StackExchange.using("snippets", function() {
            createEditor();
            });
            }
            else {
            createEditor();
            }
            });

            function createEditor() {
            StackExchange.prepareEditor({
            heartbeatType: 'answer',
            autoActivateHeartbeat: false,
            convertImagesToLinks: false,
            noModals: true,
            showLowRepImageUploadWarning: true,
            reputationToPostImages: null,
            bindNavPrevention: true,
            postfix: "",
            imageUploader: {
            brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
            contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
            allowUrls: true
            },
            noCode: true, onDemand: true,
            discardSelector: ".discard-answer"
            ,immediatelyShowMarkdownHelp:true
            });


            }
            });














            draft saved

            draft discarded


















            StackExchange.ready(
            function () {
            StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f154034%2fare-these-45-degree-wall-braces-structurally-important-or-just-for-convenience%23new-answer', 'question_page');
            }
            );

            Post as a guest















            Required, but never shown

























            2 Answers
            2






            active

            oldest

            votes








            2 Answers
            2






            active

            oldest

            votes









            active

            oldest

            votes






            active

            oldest

            votes









            2














            Temporary braces are nailed to the face of the wall, not fit into it. That was intended as a structural member by the carpenter.



            That said, it's almost certainly not critical. The entirety of the other nearby walls and the roof structure likely provide many times what that one brace does in diagonal support. Also, you don't see that technique used anymore.



            I wouldn't hesitate to remove the portion that impedes your progress.



            I do suggest a doubled stud, however, and you might want to orient at least one of your header members vertically, for stiffness.






            share|improve this answer





















            • When you say orient one header vertically, do you mean like |_ as opposed to || (looking down the long axis of the headers)?
              – TylerH
              2 hours ago
















            2














            Temporary braces are nailed to the face of the wall, not fit into it. That was intended as a structural member by the carpenter.



            That said, it's almost certainly not critical. The entirety of the other nearby walls and the roof structure likely provide many times what that one brace does in diagonal support. Also, you don't see that technique used anymore.



            I wouldn't hesitate to remove the portion that impedes your progress.



            I do suggest a doubled stud, however, and you might want to orient at least one of your header members vertically, for stiffness.






            share|improve this answer





















            • When you say orient one header vertically, do you mean like |_ as opposed to || (looking down the long axis of the headers)?
              – TylerH
              2 hours ago














            2












            2








            2






            Temporary braces are nailed to the face of the wall, not fit into it. That was intended as a structural member by the carpenter.



            That said, it's almost certainly not critical. The entirety of the other nearby walls and the roof structure likely provide many times what that one brace does in diagonal support. Also, you don't see that technique used anymore.



            I wouldn't hesitate to remove the portion that impedes your progress.



            I do suggest a doubled stud, however, and you might want to orient at least one of your header members vertically, for stiffness.






            share|improve this answer












            Temporary braces are nailed to the face of the wall, not fit into it. That was intended as a structural member by the carpenter.



            That said, it's almost certainly not critical. The entirety of the other nearby walls and the roof structure likely provide many times what that one brace does in diagonal support. Also, you don't see that technique used anymore.



            I wouldn't hesitate to remove the portion that impedes your progress.



            I do suggest a doubled stud, however, and you might want to orient at least one of your header members vertically, for stiffness.







            share|improve this answer












            share|improve this answer



            share|improve this answer










            answered 4 hours ago









            isherwood

            45k453115




            45k453115












            • When you say orient one header vertically, do you mean like |_ as opposed to || (looking down the long axis of the headers)?
              – TylerH
              2 hours ago


















            • When you say orient one header vertically, do you mean like |_ as opposed to || (looking down the long axis of the headers)?
              – TylerH
              2 hours ago
















            When you say orient one header vertically, do you mean like |_ as opposed to || (looking down the long axis of the headers)?
            – TylerH
            2 hours ago




            When you say orient one header vertically, do you mean like |_ as opposed to || (looking down the long axis of the headers)?
            – TylerH
            2 hours ago













            2














            Sometimes framing of a short internal wall that TEE's into an exterior wall is braced that way if the exterior wall is:




            1. The exterior wall extends a long distance on either side of the TEE

            2. And the exterior wall is parallel to ceiling joists and floor joists

            3. And has a high gable end wall above this area.


            Intention was to eliminate a lot of flex in the exterior wall both during construction and when there is possibility of large gusty wind loads on the wall. You will see less of this with much construction moving toward 2x6 studding for exterior walls. Metal X banding nailed to the face of the studs is also a better way to achieve this result.



            Repeating from Isherwood. Make sure to put double stud at the left and right side of your opening. A single 2x4 is just not stiff enough and you will really appreciate it being there when you come to install door casing or trim.






            share|improve this answer


























              2














              Sometimes framing of a short internal wall that TEE's into an exterior wall is braced that way if the exterior wall is:




              1. The exterior wall extends a long distance on either side of the TEE

              2. And the exterior wall is parallel to ceiling joists and floor joists

              3. And has a high gable end wall above this area.


              Intention was to eliminate a lot of flex in the exterior wall both during construction and when there is possibility of large gusty wind loads on the wall. You will see less of this with much construction moving toward 2x6 studding for exterior walls. Metal X banding nailed to the face of the studs is also a better way to achieve this result.



              Repeating from Isherwood. Make sure to put double stud at the left and right side of your opening. A single 2x4 is just not stiff enough and you will really appreciate it being there when you come to install door casing or trim.






              share|improve this answer
























                2












                2








                2






                Sometimes framing of a short internal wall that TEE's into an exterior wall is braced that way if the exterior wall is:




                1. The exterior wall extends a long distance on either side of the TEE

                2. And the exterior wall is parallel to ceiling joists and floor joists

                3. And has a high gable end wall above this area.


                Intention was to eliminate a lot of flex in the exterior wall both during construction and when there is possibility of large gusty wind loads on the wall. You will see less of this with much construction moving toward 2x6 studding for exterior walls. Metal X banding nailed to the face of the studs is also a better way to achieve this result.



                Repeating from Isherwood. Make sure to put double stud at the left and right side of your opening. A single 2x4 is just not stiff enough and you will really appreciate it being there when you come to install door casing or trim.






                share|improve this answer












                Sometimes framing of a short internal wall that TEE's into an exterior wall is braced that way if the exterior wall is:




                1. The exterior wall extends a long distance on either side of the TEE

                2. And the exterior wall is parallel to ceiling joists and floor joists

                3. And has a high gable end wall above this area.


                Intention was to eliminate a lot of flex in the exterior wall both during construction and when there is possibility of large gusty wind loads on the wall. You will see less of this with much construction moving toward 2x6 studding for exterior walls. Metal X banding nailed to the face of the studs is also a better way to achieve this result.



                Repeating from Isherwood. Make sure to put double stud at the left and right side of your opening. A single 2x4 is just not stiff enough and you will really appreciate it being there when you come to install door casing or trim.







                share|improve this answer












                share|improve this answer



                share|improve this answer










                answered 4 hours ago









                Michael Karas

                43.5k43482




                43.5k43482






























                    draft saved

                    draft discarded




















































                    Thanks for contributing an answer to Home Improvement Stack Exchange!


                    • Please be sure to answer the question. Provide details and share your research!

                    But avoid



                    • Asking for help, clarification, or responding to other answers.

                    • Making statements based on opinion; back them up with references or personal experience.


                    To learn more, see our tips on writing great answers.





                    Some of your past answers have not been well-received, and you're in danger of being blocked from answering.


                    Please pay close attention to the following guidance:


                    • Please be sure to answer the question. Provide details and share your research!

                    But avoid



                    • Asking for help, clarification, or responding to other answers.

                    • Making statements based on opinion; back them up with references or personal experience.


                    To learn more, see our tips on writing great answers.




                    draft saved


                    draft discarded














                    StackExchange.ready(
                    function () {
                    StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f154034%2fare-these-45-degree-wall-braces-structurally-important-or-just-for-convenience%23new-answer', 'question_page');
                    }
                    );

                    Post as a guest















                    Required, but never shown





















































                    Required, but never shown














                    Required, but never shown












                    Required, but never shown







                    Required, but never shown

































                    Required, but never shown














                    Required, but never shown












                    Required, but never shown







                    Required, but never shown







                    Popular posts from this blog

                    A CLEAN and SIMPLE way to add appendices to Table of Contents and bookmarks

                    Calculate evaluation metrics using cross_val_predict sklearn

                    Insert data from modal to MySQL (multiple modal on website)